Tengivirki og aðveitustöðvar

Tengivirki Búðarhálsi

Suðurland

Verkís services was project planning design, design memoranda, tender design, technical specifications and tender documents both for the civil work (mechanical and electrical part) and the substation equipment. All detail design of the substation building´s appurtenances. This includes piping, ventilation, embedded earthing and electrical installations in the building.

 Stærðir: 220 kV
 Verktími:  2011 - 2014

Almennt um verkefnið:
The substation is equipped with 220 [245] kV AIS switchgear with single main busbars. The circuit breakers are of the Disconnecting Circuit Breaker (DCB) type and no disconnectors therefore installed in the substation. The substation has three bays, two transformer bays, and one transmission line terminal without circuit breaker. The transformer bays are connected by cables to unit transformers in a nearby Hydro Power Plant. The substation is equipped with all necessary auxiliary equipment such as 400 V distribution and double 110 V DC systems. The control system is by numerical bay controllers dedicated for switchgear control and simple local SCADA system. The highest control level is from dispatch centre in Reykjavík via gateway. The protection relays are of modern numerical type.

The switchgear is located in a steel frame building for weather protection. The auxiliary equipment, control and protection equipment is located in a small concreted building.

 

Verkís was the Owner´s Engineer for all electrical design of the substation equipment and all mechanical and electrical design for the building.

The received tenders were reviewed and assistance given in contracting. The detail design of the substation equipment was made by the contractor but reviewed by Verkís.